Off-Grid Solar Calculators
Grounding Rod & Wire Sizer
https://offgridsizing.com/calculators/grounding-wire-sizer/
Engineering estimate only — not a system design. Verify with a licensed electrician.
Grounding Rod & Wire Sizer
Two different conductors. The grounding electrode conductor (GEC) runs to the rod or other electrode. The equipment grounding conductor (EGC) follows the circuit so metal cases have a fault path.
Inputs
Results
- GEC (to the electrode)
- 6 AWG
- EGC (with the circuit)
- 10 AWG
Engineering methodology
Two different conductors. The grounding electrode conductor (GEC) runs to the electrode. For a rod, pipe or plate used as the sole connection, NEC 250.166(C) says the GEC need not be larger than 6 AWG copper. For other electrodes the GEC is not smaller than the largest supplied conductor, not smaller than 8 AWG, and need not be larger than 3/0. The equipment grounding conductor (EGC) follows a simplified NEC Table 250.122 by overcurrent-device rating.
Frequently asked questions
What is the difference between a GEC and an EGC?
The GEC connects the system to the grounding electrode (rod, pipe, plate, ring). The EGC runs with the circuit so metal cases have a fault path back to the source so the OCPD can open. This tool sizes both; it does not design the whole grounding-electrode system.
Why is a ground-rod GEC capped at 6 AWG copper?
NEC 250.166(C): where connected to a rod, pipe or plate electrode, the GEC need not be larger than 6 AWG copper. A 4/0 battery cable does not force a 4/0 GEC to a single rod.
Does Table 250.122 apply to DC off-grid systems?
EGC sizing by OCPD rating is the usual NEC approach this tool copies in simplified breakpoints. DC bonding of negative, chassis and AC equipment grounds is a separate design choice for a qualified electrician.
More in this cluster
All wiring and electrical safety toolswiring
DC Inline Fuse & Circuit Breaker Sizer
Size a DC fuse or breaker at 125% of continuous current, then check it against copper cable ampacity.
wiring
DC Voltage Drop Calculator
Calculate copper DC voltage drop in volts and percent for a chosen AWG, current and one-way cable length.
wiring
12V/24V/48V DC Wire Gauge (AWG) Calculator
Pick a copper AWG size for 12V, 24V or 48V DC runs from current, one-way length and a 3% voltage-drop budget.
wiring
Solar Combiner Box Fuse Sizer
Size PV string and combiner fuses at 1.56 × Isc and see when three or more parallel strings need fusing.